HomeMy WebLinkAboutRES CC 2016 3552 2016 1102 RESOLUTION NO. 2016-3552
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF
MOORPARK, CALIFORNIA, RATIFYING CHAPTER 9 OF
VENTURA COUNTY FIRE PROTECTION DISTRICT
ORDINANCE NO. 30, PERTAINING TO BUILDING
STANDARDS FOR APPLICATION WITHIN THE
JURISDICTIONAL BOUNDARIES OF THE CITY OF
MOORPARK, AND RESCINDING RESOLUTION NO. 2013-
3251
WHEREAS, the City of Moorpark lies within the jurisdictional boundaries of the
Ventura County Fire Protection District and the Ventura County Fire Protection District
has responsibility for fire protection within said jurisdictional boundaries; and
WHEREAS, on October 25, 2016, the Ventura County Fire Protection District
adopted Fire Protection District Ordinance No. 30, adopting the 2016 California Fire
Code and the 2015 edition of the International Fire Code by reference, together with
portions of the Appendix Chapters thereof, and amendments thereto; and
WHEREAS, Chapter 9 of said amendments constitutes amendments to building
standards relating to fire and panic safety adopted by the State Fire Marshal and
contained in the California Building Standards Code; and
WHEREAS, pursuant to Section 13869.7(c) of the California Health and Safety
Code, amendments containing such building standards are not effective within the
jurisdictional boundaries of the City until ratified by the City Council; and
WHEREAS, said Chapter 9 contains similar building standards that have been in
effect and enforced within the current City boundaries since June 3, 1982, prior to
incorporation; and
WHEREAS, the building standards contained within. Chapter 9 are an integral
part of the Ventura County Fire Protection District fire protection response plan; and
WHEREAS, City Council Resolution No. 2013-3251 previously ratified Appendix
L of Fire Protection District Ordinance No. 28, which was superseded by Fire Protection
District Ordinance No. 30, and as such will no longer be valid and should be rescinded
upon the effective date of Fire Protection District Ordinance No. 30.
NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF MOORPARK
DOES HEREBY RESOLVE AS FOLLOWS:
SECTION 1. CITY COUNCIL RATIFICATION: The City of Moorpark ratifies,
without modification, Chapter 9 of Ventura County Fire Protection District Ordinance No.
Resolution No. 2016-3552
Page 2
30 to be effective within the jurisdictional boundaries of the City of Moorpark on and
after January 1, 2017.
SECTION 2. Resolution No. 2013-3251 is hereby rescinded in its entirety,
effective January 1, 2017.
SECTION 3. The City Clerk shall certify to the adoption of this resolution and
shall cause a certified resolution to be filed in the book of original resolutions.
PASSED AND ADOPTED this 2nd day of November, 2016.
•
Janice S. Parvin, Mayor
ATTEST: ..
OS 4
Maureen Benson, City Clerk 0 1416 .
47,
fLr2 31)N'
Exhibit A: Chapter 9 of Fire Protection District Ordinance No. 30
Resolution No. 2016-3552
Page 3
EXHIBIT A
VENTURA COUNTY FIRE PROTECTION DISTRICT ORDINANCE NUMBER 30
CHAPTER 9
FIRE PROTECTION SYSTEMS
Section 901.11 is added to read as follows: -
901.11 Working space and clearance. A working space of not less than 30 inches
(762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1,981 mm) in height
shall be provided in front of fire protection equipment including, but not limited to: fire
sprinkler control valves, fire department connections, hose connections, risers, hood
system manual pull stations, fire alarm control panels, fire pumps, and specialized fire
protection storage tanks (dry chemical, foam, CO2, clean agent). Where the fire
protection equipment is wider than 30 inches (762 mm), the working space shall not
be less than the width of the equipment. No storage of any materials shall be located
within the designated working space. Direct access to the working space shall be
provided from aisles or access roadways. Modifications to working space dimensions
shall be approved by the Fire Code Official.
Section 903.1.2 is added to read as follows:
903.1.2 Concurrent permits. Additions or modifications where the application for a
building permit is submitted prior to the final inspection of any previously issued
building permit(s) shall require the installation of an automatic fire sprinkler system
throughout the entire Structure when the area of the addition or modification of all
open permits combined with the new application exceed the exceptions listed under
Section 903.2.
Section 903.1.3 is added to read as follows:
903.1.3 Fire walls. For the purposes of this Chapter, fire walls shall not be
considered as creating separate Buildings.
Section 903.1.4 is added to read as follows:
903.1.4 Modifications prohibited: When an automatic fire sprinkler system is
installed in accordance with NFPA 13R in Group R Occupancies, allowable increases,
reductions in or exceptions to code requirements shall not be permitted.
Section 903.1.5 is added to read as follows:
903.1.5 Maintenance of area separation walls. Area separation walls used to
create fire areas less than 5,000 square feet of floor area (5,000 Gross Square Feet
for Group R-3 Occupancies) in Buildings constructed under the original accepted
Resolution No. 2016=3552
Page 4
building permit application dated prior to November 1, 2002 shall be maintained with
no openings as approved. If the approved walls are not maintained, the Building shall
be retro-fitted with an approved automatic fire sprinkler system. Additions to any
Building shall not exceed 25% of the legally existing floor area and shall not cause any
fire area to equal or exceed 5,000 square feet, unless an approved automatic fire
sprinkler system is provided in the entire Building.
Section 903.1.6 is added to read as follows:
903.1.6 Previously exempted. Any Existing Building with less than 701 square feet
or floor area (701 Gross Square Feet for Group R-3 Occupancies) previously exempt
from fire sprinklers that would have been required to mitigate fire flow, access
requirements, or distance to a fire station at the time the building permit was issued,
shall provide fire sprinklers within the entire Building when any addition to the Building
brings the total square footage over the previous exempt amount of 700 square feet,
regardless of the percent of the addition. Allowances in Section 903.2 item number 2
shall not apply.
Section 903.1.7 is added to read as follows:
903.1.7 Change of use. Any change of use of a Group U Occupancy, that
reclassifies to a new occupancy classification that would not have been exempt from
fire sprinklers due to existing size, use, fire flow, access requirements, or distance to a
fire station under a previous Fire District Ordinance in effect at the time the building
permit was issued, shall provide fire sprinklers within the Existing Building. Allowance
in Section 903.2 item number 2 shall not apply. This section does not limit the
requirements for fire sprinklers for the new occupancy classification under the current
California Building and Fire Codes.
Section 903.2 is amended to read as follows:
903.2 Where required. Notwithstanding the provisions of 903.1.2 through 903.1.7
and 903.2.1 through 903.2.12 an approved automatic fire sprinkler system shall be
installed in Buildings and Structures as follows:
1. An automatic fire sprinkler system shall be installed in all New Buildings.
Exceptions:
A. Group U Occupancies when approved by the Fire Code Official.
B. Small agricultural produce stands as defined and constructed in
accordance with the current edition of the Ventura County Building
Code (VCBC) which comply with all of the following:
1. Floor area of the Structure does not exceed 400 square feet
Resolution No. 2016-3552
Page 5
2. Separated from other Buildings a minimum of 30 feet
C. Picnic and lunch shelter Structures which comply with all of the
following:
1. Use is defined as a Group A, Division 2 or 3 Occupancy by the
Building Department
2. Shall not exceed 1,500 square feet of floor area for an A-2
Occupancy or 4,500 square feet for an A-3 Occupancy
3. Separated from other Buildings a minimum of 30 feet
4. Only picnic tables and chairs are located underneath the
shelter
5. Shall not have any enclosed space underneath the shelter
covering
6. Shall be located at grade level around the entire shelter
7. Open on all sides from finished grade to a height of 10 feet
above finished grade
8. Structural columns and other architectural features may not
obstruct more than 10% of the opening length around the
Structure
9. Shall have no obstructions that will hinder egress within 10 feet
of the exterior perimeter of the shelter for a distance of 75% of
the opening length around the shelter
10. A food preparation surface area may be located along one
opening, but shall not obstruct more than 20 feet or 10% of the
opening length, whichever is less
11. May be constructed of any materials allowed by the California
Building Code (CBC)
12. Any roof covering shall be non-combustible if not an open trellis
style shelter.
D. S-2 Carport Structures which comply with all of the following:
1. Buildings or Structures shall be freestanding and legally
separated from all other Buildings or uses
2. Building shall be constructed of non-Combustible Materials
3. Fire apparatus access shall extend to within 25 feet of all
Resolution No. 2016-3552
Page 6
portions of the interior of the Carport as measured by an
approved route around the exterior of the Building or Structure
2. An approved automatic fire sprinkler system shall be installed in Buildings or
Structures with additions as determined by the following:
A. Additions to legally existing Group R-3 Occupancies, inclusive of
attached Group U Occupancies where the addition is both greater than
1,000 square feet and greater than 50% of the existing legal Gross
Square Feet of the Structure
B. All occupancies other than Group R-3, where an addition is greater
than 25% of the legally existing floor area of the Structure
Exception: Group U Occupancies when approved by the Fire Code
Official
C. Where additions to Existing Buildings or Structures increase the
allowable area beyond that permissible in Section 903.2.1 through
903.2.12 for non-sprinklered Buildings
3. Change of use shall require fire sprinklers in accordance with Sections
903.2.1 through 903.2.12.
Section 903.2.8.1.1 is added to read as follows:
903.2.8.1.1 Coverage. Automatic fire sprinkler systems installed in accordance with
NFPA 13D in Group R-3 Occupancies shall provide sprinkler protection of attached
Group U Occupancies.
- End -
Resolution No. 2016-3552
Page 7
STATE OF CALIFORNIA )
COUNTY OF VENTURA ) ss.
CITY OF MOORPARK )
I, Maureen Benson, City Clerk of the City of Moorpark, California, do hereby
certify under penalty of perjury that the foregoing Resolution No. 2016-3552 was
adopted by the City Council of the City of Moorpark at a regular meeting held on the 2nd
day of November, 2016, and that the same was adopted by the following vote:
AYES: Councilmembers Mikos, Millhouse, Pollock, Van Dam, and Mayor Parvin
NOES: None
ABSENT: None
ABSTAIN: None
WITNESS my hand and the official seal of said City this 10th day of November,
2016.
Maureen Benson, City Clerk